Ladder - Conveyor Jam Watchdog
Six rungs where the photo-eye has been blocked for 8 s against a 6 s TON preset, so the jam latches on rung 4 after the belt coil was already solved true on rung 2 -- the one-scan lag that makes a real controller keep the belt running for one more pass -- with the beacon and horn coils drawn in series off the same latched fault.
Make it your own.
title "Belt conveyor - photo-eye jam detection"
state: Run_Cmd, E_Stop_OK, Guard_Closed, Eye_Blocked, Jam_Reset=0
rung "Safety chain must be healthy before anything runs"
xic E_Stop_OK
xic Guard_Closed
ote Safe
rung "Belt runs on command while safe and not jammed"
xic Run_Cmd
xic Safe
xio Jam_Fault
ote Belt_Motor
rung "Photo-eye blocked longer than 6 s while running is a jam"
xic Belt_Motor
xic Eye_Blocked
ton T_Jam preset: 6 accum: 8 unit: s
rung "Latch the jam fault - it must survive the belt stopping"
xic T_Jam.DN
otl Jam_Fault
rung "Panel reset is the only way out of the latch"
xic Jam_Reset
otu Jam_Fault
rung "Beacon and horn, two coils in series off one fault"
xic Jam_Fault
ote Beacon
ote Horn